How to Select Industrial Valves for Power Plants

UTC valve beside cooling towers at a power generation plant

A thermal power plant is, in effect, a large network of pipes carrying water and steam at changing temperatures and pressures. The valves in that network must open and close reliably over decades, tolerate repeated heat-up and cool-down cycles, and resist erosion from fast, wet or contaminated flow. A valve that is adequate in a water treatment plant can fail early in a steam line.

This article goes through the main systems in a power plant, the valve duties in each, and the factors that drive material, design and standard selection.

Valve duties by plant system

SystemTypical dutyCommon valve types
Main steam and hot reheatIsolation at high pressure and temperaturePressure seal gate and globe valves
Boiler feedwaterIsolation, non-return, control bypassPressure seal gate, globe and check valves
Condensate and low-pressure steamIsolation and regulationGate, globe and check valves
Auxiliary steamIsolation and drainsGate, globe, forged steel valves
Cooling waterLarge-diameter isolation and controlGate and butterfly valves, strainers
Fuel oil and gasIsolation and shut-offGate, globe and ball valves
Fire waterIsolation and non-returnGate and check valves
Drains, vents and instrument linesSmall-bore isolationForged gate, globe and check valves

Conditions that drive selection

Temperature and thermal cycling

Power plants start up and shut down, sometimes daily. Each cycle expands and contracts valve bodies, bonnets and piping. Flexible wedge gate valves resist sticking caused by body distortion, and pressure seal bonnets keep their seal under cycling. Warm-up and drain arrangements, such as bypasses, help to reduce thermal shock.

Pressure

Main steam and feedwater lines operate at high pressure, which usually calls for higher pressure classes. See our guide to pressure classes for how ratings fall with temperature.

Erosion and corrosion

Wet steam and high-velocity flow erode seats and bodies. Flow-accelerated corrosion can thin carbon steel in some feedwater and wet steam systems, so material choice and water chemistry matter. Hard-faced trims extend seat life, and alloy steels resist erosion better than plain carbon steel.

Materials for high-temperature service

Carbon steel such as ASTM A216 WCB is common at moderate temperatures, but it is generally limited in long-term high-temperature service because of material behaviour at elevated temperature. Chrome-moly alloy steels, such as ASTM A217 WC6 and WC9 for castings and A182 F11 and F22 for forgings, are used for higher-temperature steam. The specific grade and its allowable temperature should be taken from ASME B16.34 and the plant piping specification. Confirm grade availability with the supplier for each enquiry.

Why pressure seal valves are common here

High-pressure steam and feedwater lines are the classic application for pressure seal bonnets. The seal tightens as pressure rises, and the body avoids the large bolted bonnet flange. Read what a pressure seal valve is for the operating principle, or view our pressure seal valves page.

Check valves and pump protection

Boiler feed pumps and condensate pumps need non-return valves that close quickly enough to limit surge and reverse flow. Lift-type, tilting-disc and spring-assisted designs are used depending on the system. See how to choose a check valve for the factors involved. A strainer at pump suction or on feed lines protects pumps and control valves from debris, particularly during commissioning.

Standards and codes

Power piping is normally designed to ASME B31.1, which sets the rules for piping systems in power plants. Valve ratings follow ASME B16.34, and valve design and testing follow standards such as API 600 (steel gate valves), API 623 or BS 1873 (globe valves), API 602 (small forged valves) and API 598 (testing). The project specification and the owner’s engineer decide which editions and additional requirements apply, so match your enquiry to them.

Operation, automation and maintenance

Large gate and globe valves on steam lines are normally actuated, and the actuator must handle the stem thrust, particularly at maximum differential pressure. Include actuator type and operating time in the data sheet. Plan for access, because valves on high-pressure lines are heavy and difficult to remove during an outage. Standardising on a limited number of valve designs across units also reduces spares and training needs.

Selection steps

  1. List the system, fluid and phase.
  2. Define design and operating pressure and temperature, including upset conditions.
  3. Choose valve type according to duty: isolation, regulation or non-return.
  4. Select pressure class and material from ASME B16.34 and the piping specification.
  5. Decide bonnet type: bolted or pressure seal.
  6. Specify trim, end connections and operator.
  7. State standards, tests and documents required.
  8. Send the data through Request a Quote.

Commissioning and start-up considerations

New steam lines are normally cleaned by steam blowing before commissioning to remove weld spatter, scale and debris. Valves in those lines must be protected, either by temporary spools or by following the commissioning procedure, so that debris does not damage seats. Warm-up should be gradual, with drains open, to reduce thermal shock. Check that every valve moves freely through its full travel before pressure is applied, and record packing and bonnet checks during the first heat cycle. These steps often matter as much as the original valve selection.

Documentation for power projects

Power plant specifications usually require material certificates, test reports, valve data sheets and drawings, and operating and maintenance manuals. Boilers and high-energy piping may also be subject to local regulation, which can add requirements for documentation and inspection. Ask the supplier early what can be provided so that submittal schedules are realistic. Our quality and standards page explains the approach to documentation.

Questions to settle before ordering steam valves

  • What are the normal, maximum and upset design pressures and temperatures?
  • Will the valve see frequent start-up and shutdown cycles?
  • Is the line subject to wet steam or high-velocity flow that could erode seats?
  • Does the specification require a bolted or a pressure seal bonnet?
  • What trim hardness is expected, and is hard-facing required on the seating faces?
  • Will the valve be actuated, and what stem thrust or torque is expected?
  • Which documents and tests does the plant owner require?

Answering these early shortens the quotation process and reduces the risk of ordering a valve that needs rework during an outage.

Where our range fits

UTC VALVES manufactures and supplies gate valves, globe valves, check valves, pressure seal valves and forged steel valves for industrial and power applications. Each enquiry is reviewed for availability and specification before a quotation is issued.

Frequently asked questions

Which valves are used on main steam lines?

High-pressure isolation is usually by pressure seal gate or globe valves, chosen for the pressure class and temperature.

Why are flexible wedge gate valves used in steam?

The flexible wedge accommodates body distortion caused by thermal cycling, which reduces the risk of sticking.

What code applies to power plant piping?

ASME B31.1 is the common code for power piping.

Do power plant valves need actuators?

Large valves are often actuated for remote operation and to handle high stem thrust.

References and further reading

Standards and codes are published by their issuing bodies. Always use the current edition named in your project specification.

UTC VALVES Editorial Team
Technical articles prepared for engineers, procurement teams and EPC contractors. This content is for general information; always follow your project specification and the current edition of the applicable standards.

Related articles

All articles

Looking for a Reliable Valve Manufacturer?

Send your specification, datasheet or bill of materials. Our team reviews every enquiry and responds with availability and a quotation.

Request a Technical Quotation
WhatsApp us